Link to main IT standards page
Welcome to the SMCCD IT standards web site
Link to cable specifications Link to wireless specifications Link to instructional technologies Link to athletic facilities specifications Link to descriptions of recent projects Link to equipment information page Link to IT staff contact information
Wireless Standards

Instructional Standards

Athletic Facilities

Projects

Equipment Information

Contacts

Ask a Question??

Cabling Standards: Communications Conduits & Information Outlets, Communications Pathways Specifications

Download PDF Version Cabling Standards

Cabling Standards Section Links

Introduction Communications Conduits and Information Outlets <=
Certifications & Req. Deliverables Communications Pathways Specifications <=
General Overview Per-Floor Telecommunications Wiring Systems
Service Entrance & Termination Room MDF Building Riser Specifications
Equipment Rooms (MDF/IDF) Grounding and Lightning Protection
Per-Floor Telecommunications Room (IDF) Power

Communications Conduits & Information Outlets

The minimum conduit and outlet specifications for District’s communication cabling system are as follows:

  • Communication Entrance Conduits: The communication entrance conduit shall consist of at least two (2) four inch (4") conduits run from the nearest existing manhole or pull-box, to the Service Entrance and Termination Room of the new facility.
  • This run of conduit shall not contain more then two 90-degree bends and be placed with a minimum of 1/4 inch per foot slope to allow proper water drainage from the ducts.
  • No run of conduit shall exceed 300 feet between pull-boxes or manholes.
  • New manholes shall contain permanent ladders, pull rings, grounding system, a sump pit, and a floor drainage system to drain water.
  • New pull-boxes shall contain, pull rings, grounding system, a sump pit, and a floor drainage system to drain water.
  • Other Outdoor Communication Conduits: Conduit run outdoors for other communication purposes shall be a minimum of one-inch diameter, and be placed with a minimum of 1/4 inch per foot slope to allow proper water drainage from the ducts.
  • No run of conduit shall exceed 300 feet between pull points and contain no more then two 90-degree bends.
  • If pull-boxes are installed the conduits shall enter the pull-box one foot above the bottom and the pull box shall have a means to drain water from them.
  • Service Entrance: The conduits entering from outside of the building shall terminate 4 inches after they penetrate the outside wall. Cable tray shall be installed from the penetration point to the Service Entrance and Termination Room. A ground wire with buss bar shall be installed at the location the cable enters the building.
  • Voice and/or Data Connections: At least two Cat. 6 outlet boxes with a minimum of two Cat. 6 cables per box shall be installed on opposite walls within every classroom. There shall be two outlet boxes containing three Category 6 jacks in each office unless otherwise designated by ITS. Boxes should be installed on opposite walls.
  • Conduit from Outlets: A one-inch conduit shall connect the four jack Category 6 outlet box to the nearest cable tray or J-hook. The conduit shall terminate within 4 inches of the nearest cable tray or J-hook. The minimum size conduit run from the telecommunication outlet to the nearest cable tray of J-hook shall be a one-inch EMT conduit.
  • Conference Rooms: One outlet box with four Category 6 jacks and the corresponding one-inch conduit shall be installed in every conference room and be connected directly to the Telecommunication Room on that floor as designated by ITS.
  • Security & Fire Alarm Telecommunication Conduits: Conduit installed for Security and Fire Alarm shall be a 1” EMT conduit and be a home run back to the Telecommunications Room and shall have a pull box after every 180-degree change in direction or elevation or every 150 feet.
  • Conduit runs shall not exceed 295 feet in length.
  • Provide pull boxes in readily accessible locations. The installation of pull boxes in the conduit run shall be placed in line with the conduit run such that wire or fiber-optic cable can be pulled through the pull box without incurring damage to the cable. No turns or bends of the conduit run are allowed with pull boxes.
  • Public Telephones: Conduit installed for payphones, emergency phones and elevator phones shall be a ¾” EMT conduit and be a home run back to the Telecommunications Room and shall have a pull box after every 90 degree change in direction or elevation or every 150 feet.
  • Conduit runs shall not exceed 295 feet in length.
  • Provide pull boxes in readily accessible locations. The installation of pull boxes in the conduit run shall be placed in line with the conduit run such that wire or fiber-optic cable can be pulled through the pull box without incurring damage to the cable. No turns or bends of the conduit run are allowed with pull boxes.
  • Bending Restrictions: Minimum radius for bends shall be 9-1/2 inches for 3/4-inch conduit, 10-1/2 inches for one inch conduit and the equivalent of long radius factory bends for larger sizes. The short radius bends of larger diameter conduit normally installed for electrical installations is not sufficient for communication cabling. Four (4) inch conduit installed for communication cabling shall have a four foot radius bend.
  • Labeling: The contractor is expected to provide tags, straps, and adhesive labels. These tags, straps, and adhesive labels must be of high quality that will endure over time.  Hand written labels are not acceptable.  The contractor is required to provide labels for all station cable at ten inches of the termination ends, using Brady type self-laminating cable markers or equal.  Station cables will be labeled on both ends with the wall plate numbers according to the ITS labeling standardsLabel all pull and junction boxes consistent with ITS standards and naming conventions.
  • Pull Cords: Provide a nylon pull cord in each empty conduit with a 200 pound pulling tension.
  • Fiber-optic Cabling: Conduit installation for communication purposes shall be installed with the probability of fiber-optic cable being installed in it and pulling tension and minimum bend radius being critical factors for installing usable fiber-optic cable as well as the Category 6 cable.

Communications Pathways Specifications

The standards adopted by the District provide that a clear and accessible pathway for horizontal telecommunications cabling be provided. These pathways are located between the Telecommunications Rooms and the rooms/offices containing the voice and/or data outlets. The Design Team consultants shall prepare drawings and specifications that insure a clear and accessible pathway for telecommunications wiring. Any pathway that is not accessible or does not provide a clear and workable pathway will need to be removed and reinstalled to provide a clear and accessible pathway.

There are several methods available for providing a pathway for supporting telecommunications cables. The architectural design of each building is unique and requires an analysis of which method(s) are best suited for that building.  J-Hooks are the preferred method of providing a pathway. Cable trays may be used and in many instances may be preferred. Each type is listed below.

  • Cable Trays: The cable tray size(s) will be determined during the design phase of the project. The cable tray shall be installed in accordance with the applicable electrical code. The cable tray is to be dedicated for use only by ITS. No other cabling is to share the cable tray without the approval of ITS.  There are three manufacturers recommended for cable trays as shown below, however, an equivalent quality cable tray can be substituted:
    • MONO-Systems, Inc., "MONO-Tray" system
    • B-Line Systems Inc., "Cent-R-Rail" system
    • Chatsworth, “Cable Runway system”
  • J-Hooks:  The model to use will be determined by the number of cables in that pathway. No other cabling is to share the J-Hooks with ITS. There are two manufacturers recommended for J-hooks, however, an equivalent quality J-hook can be substituted:
    • B-Line Systems, Inc.; Models BCH21, BCH32, and BCH64
    • Erico Fastening Products, "CableCat" system; Models Cat21 and Cat32
 

 

Cabling Standards Section Links

Introduction Communications Conduits and Information Outlets <=
Certifications & Req. Deliverables Communications Pathways Specifications <=
General Overview Per-Floor Telecommunications Wiring Systems
Service Entrance & Termination Room MDF Building Riser Specifications
Equipment Rooms (MDF/IDF) Grounding and Lightning Protection
Per-Floor Telecommunications Room (IDF) Power

 

Updated February 9, 2006