Link to main IT standards page
Welcome to the SMCCD IT standards web site
Link to cable specifications Link to wireless specifications Link to instructional technologies Link to athletic facilities specifications Link to descriptions of recent projects Link to equipment information page Link to IT staff contact information
Wireless Standards

Instructional Standards

Athletic Facilities

Projects

Equipment Information

Contacts

Ask a Question??

Cabling Standards: Service Entrance and Termination Room (MDF)

Download PDF Version Cabling Standards

Cabling Standards Section Links

Introduction Communications Conduits and Information Outlets
Certifications & Req. Deliverables Communications Pathways Specifications
General Overview Per-Floor Telecommunications Wiring Systems
Service Entrance & Termination Room MDF <= Building Riser Specifications
Equipment Rooms (MDF/IDF) Grounding and Lightning Protection
Per-Floor Telecommunications Room (IDF) Power

Service Entrance and Termination Room (MDF)

This type of telecommunications room is the required service entrance for telecommunications services (voice and data). The number and size of inter-building conduits to this room will be determined by the number and type of telecommunications terminations that will be brought into the building.

In general, MDF entrance doors should open out to minimize the loss of useable space within the MDF.

The minimum size and number of conduits to a building is two 4” conduits. The location shall be within 50' of the point where the electrical facilities enter the building.  Where possible, this room will be dedicated for use by ITS for network support and services. 

The basic requirements for a Service Entrance and Termination Room are as follows.

  • Required Area:
  • Minimum area is 6' X 6' for a MDF with less than 100 voice and/or data connections.
  • Minimum area is 6' X 8' for a MDF with 100 – 200 voice and/or data connections.
  • Minimum area is 8' X 10' for a MDF with 200 to 300 voice and/or data connections.
  • Minimum area is 10’ X 12’ for a MDF with > 300 voice and/or data connections.
  • Height: Minimum ceiling height is 9' 6", with the bottom of the exposed structure considered the ceiling.
  • Conduits/Sleeves: Location, number, and size of conduits and sleeves between the Service Entrance and Termination Room, Equipment Rooms, and Telecommunications Rooms will be provided during the design phase of the project. Conduits and sleeves shall extend 4" above floor level or through the wall. For most buildings this will be two 4” conduits between the Service Entrance and Termination Room, Equipment Rooms, and Telecommunications Rooms.
  • Door: Rooms shall have a fully-opening, lockable door which is at least 36" wide and 80" in height.
  • Interior Finishes: To minimize dust, floors shall be vinyl composition tile and all exposed concrete, brick and gypsum board walls shall be painted or sealed.
  • HVAC: Rooms shall have HVAC to control temperature and humidity, unless the facility can maintain the temperature in the room at a range of 65 to 85 degrees with all installed equipment powered on and operating. The specific BTU's of heating and cooling to be provided will be specific to each building. Humidity shall be controlled at 50% +/- 15%.
  • Plumbing: Service Entrance and Termination rooms should not have any water pipes within the room's interior space, routing horizontally on the floor directly above the room, or within the floor slab below the room.
  • Grounding: Provide a building ground wire, with bus bar, to the room. Locate the bus bar at the lower left corner of the plywood backboard. ITS will indicate on which backboard to place the bus bar. Refer to Grounding section of these standards.
  • Lighting: Provide minimum lighting to be equivalent of 540 lux (50 footcandles) measured 3 feet AFF.
  • Plywood Backboard Panels: Each wall that has an equipment rack or cable ladder attached to it, shall have 3/4" X 4' X 8' sheets of A-C Grade, Fire-Retardant-treated plywood installed on them for anchoring termination strips and other devices.
  • The plywood shall reach from corner to corner. Install the plywood vertically at 6" AFF and anchor securely to wall substrate with a minimum of five (5) equally spaced fasteners along each vertical edge and down the centerline of each sheet of plywood.
  • Fasteners shall be of the appropriate type for each substrate. Provide blocking or additional studs in framed walls to receive plywood backup panel fasteners.
  • Paint the plywood with two coats of fire retardant low-gloss, light-colored paint.
  • Electrical: On each wall, except the wall containing the door, install two A/C 20-amp electrical four-plex outlets, evenly spaced. Refer to Power section of these standards.
  • Floor Loads: Floors shall be designed to support 100 lbs per square foot at a minimum.
  • Telecommunication Rack(s): Install an 8’ tall and 19” wide telecommunications rack, without panels, to support fiber and cable termination devices and network electronics. Locate the rack in the room so that there is sufficient space to work behind it for installation and maintenance.  Fasten the rack to the floor and bond the rack to the ground bus. Location and manufacturer of the rack will be identified by ITS during the design phase of the project.  Install an electrical four-plex outlet in the rack to support a UPS which will be located on the floor within the rack. The size of the UPS and type of the receptacle will be determined during the design phase.

Download Example of MDF and Rack Layouts http://www.smccd.net/accounts/itwirespecs/img/RackLayouts.pdf
Download Example of MDF and IDF floor palns
http://www.smccd.net/accounts/itwirespecs/img/mdf_idf_floorplans.pdf
Download Example MDF Rack Layouts
http://www.smccd.net/accounts/itwirespecs/img/MDF_Rack_layouts.pdf

Cable Tray: Install cable tray from the cabinet to the plywood backboard. Bond the cable tray to the ground bus. Location and manufacturer of the cable tray will be identified by ITS during the design phase of the project.

Room Size Verification: When the Service Entrance and Termination Room is also used as an Equipment Room and/or Telecommunications Room, the size of the room shall be sufficient to accommodate the type and number of the services being supplied to the building. ITS will provide the size of the room, based on the type and amount of services required to support the building. ITS will also take into consideration the intended use of the building when determining the size of the Service Entrance and Termination Room.

 

 

Cabling Standards Section Links

Introduction Communications Conduits and Information Outlets
Certifications & Req. Deliverables Communications Pathways Specifications
General Overview Per-Floor Telecommunications Wiring Systems
Service Entrance & Termination Room MDF <= Building Riser Specifications
Equipment Rooms (MDF/IDF) Grounding and Lightning Protection
Per-Floor Telecommunications Room (IDF) Power
 

 

Updated February 9, 2006